Drop-out fuses for environmental overview

Dec 12, 2018

10kV drop-out fuses are suitable for outdoor environments where ambient air is free of conductive dust, non-corrosive gases, and flammable and explosive. The annual temperature difference is within ±40 °C. The choice is based on rated voltage and rated current. The two parameters are carried out, that is, the rated voltage of the fuse must match the rated voltage of the protected device (line), the rated current of the fuse device should be greater than or equal to the rated current of the melt, and the rated current of the melt can be selected as 1.5 to 2 times the rated load current. In addition, the selected fuse should be checked according to the three-phase short-circuit capacity of the protected system to ensure that the three-phase short-circuit capacity of the protected system is less than the upper limit of the rated breaking capacity of the fuse, but must be greater than the lower limit of the rated breaking capacity. If the rated breaking capacity of the fuse (generally the upper limit) is too large, it is likely that the three-phase short-circuit capacity of the protected system is less than the lower limit of the rated breaking capacity of the fuse, which makes it difficult to extinguish the arc when the melt is blown. Some electric power supply units are still at the peak of agricultural network transformation. When selecting such fuses, the quality of the products must be strictly controlled, and the qualified equipment should be connected to the network, and its rated disconnection capacity should be noted. Upper and lower limits.